minus gif view products
 |   |   | 
Logo
Image1

Acoustical Series Smoke Vents – SVX

Nystrom Acoustical Series smoke vents are a rooftop venting system that automatically opens - releasing heat, smoke, and noxious fumes during a fire. Each smoke vent will open automatically when a fusible link inside the vent reaches its melting temperature. Smoke vents are spring-operated to open against a 10 psf snow load.

SVX Acoustical smoke vents feature:

  • Innovative, upward opening, single-layer door construction
  • Energy-efficient R13 insulation for optimal envelope performance
  • Acoustical ratings to STC 45 & OITC 37
  • UL793 Listed and FM 4430 Approved
Quick Spec

Cover & Liner

14 gauge galvanized steel cover is stiffened to withstand a live load of 40 psf

12 gauge galvanized steel liner

Curb

14 gauge galvanized steel, 13" high curb, 4.75" mounting flange, 0.50" diameter mounting holes

Latch

Zinc-plated steel tandem pyrolatches with 165F fusible link, interior and exterior manual pull handles. Designed to hold covers closed against a 90psf wind uplift.

Spring/Hinge

High pressure gas spring and hinge pack designed to automatically open vent against a 10psf snow load.

Insulation

3" R13 insulation in cover and curb

Finish

Gray powder coat


Image2

Order Guide


Nystrom, Inc.
9300 73rd Ave N
Brooklyn Park, MN 55428
Phone: 800.547.2635
Fax: 800.317.8770
Email: info@Nystrom.com
Website: www.Nystrom.com





 |   |   |