The McGraw-Hill Companies
McGraw Hill Construction - Building Materials, Products and Manufacturers
home |
product centers
| find a rep |
utilities
| education | project network | SNAP Reader Service | forums
Follow us on Twitter
register | forgot password | remember me | help
 
MasterFormat   help
 
Product Center Image
 |   |   | 


Hochiki Conventional Fire Alarm Panels are microprocessor-based units designed for commercial, institutional and industrial applications. The systems are cost effective and extremely reliable. They work with conventional detection modules, bases and special purpose sensors. Please see the Detectors Products Section for further details.

HCP-204E 4-Zone Expandable Fire Alarm Control Panel
  • 4 Class B (Style B) Initiating Circuits which may be configured as 2 Class A (Style D) circuits. Expandable up to 8 Class B (Style B) or 4 Class A (Style D) Initiating Circuits
  • 2 Class A/B (Style Z/Y) Indicating Circuits with individual trouble indicators (1.7 Amps max. per circuit). Expandable up to 4 Class A/B (Style Z/Y) Indicating Circuits
  • Each Indicating Circuit can be configured as Silenceable or Non-Silenceable. Audibles may be configured as Steady, Temporal Code, California Code or March Time
  • Output for RTI or Remote Annunciators of 24 VDC, 300 mA max, unfiltered
  • Built-in Walk Test operation
  • Auxiliary relay contacts for Common Alarm, Common Trouble and Common Supervisory. If no Supervisory circuits are enabled, the Supervisory relay becomes a second alarm relay
  • 6 Amp power supply
  • Easy configuration via DIP switches
HCP-204 4-Zone Fire Alarm Control Panel
  • 4 Class B (Style B) Initiating Circuits which may be configured as 2 Class A (Style D) circuits
  • 2 Class A/B (Style Z/Y) Indicating Circuits with individual trouble indicators (1.25 Amps max. per circuit)
  • Each Indicating Circuit can be configured as Silenceable or Non-Silenceable. Audible may be configured as Steady, Temporal Code, California Code or March Time
  • Selectable alarm verification on initiating circuits
  • Output for 4-wire resettable regulated smoke power supply of 24 VDC 100 mA maximum
  • Output for RTI or Remote Annunciators of 24 VDC, 300 mA max, unfiltered
  • Built-in Walk Test operation
  • Auxiliary relay contacts for Common Alarm, Common Trouble and Common Supervisory. If no Supervisory circuits are enabled, the Supervisory relay becomes a second Alarm relay
  • 2.75 Amp power supply
  • Easy configuration via DIP switches
HCP-1008E 8-Zone Expandable Fire Alarm Control Panel
  • 8 Class B (Style B) Initiating Circuits which may be configured as 4 Class A (Style D) Circuits. Expandable up to 64 Class B or 32 Class A Initiating Circuits
  • 4 Class A/B (Style Z/Y) Indicating Circuits with individual trouble indicators (1.7 Amps max. per circuit)
  • Each Indicating Circuit can be configured as Silenceable or Non-Silenceable. Audible may be configured as Steady, Temporal Code, California Code or March Time
  • Each Initiating Circuit can be configured as Alarm, Supervisory, Waterflow or Trouble
  • Two outputs for 4 wire resettable smoke power supply (200 mA max. each)
  • Alarm verification on Initiating Circuits
  • Easy configuration via push buttons and SLIDE switches on the front panel


For Additional Information:
Hochiki America Corporation
7051 Village Drive, Suite 100
Buena Park, CA 90621-2268
(714) 522-2246
sales@hochiki.com
www.hochiki.com



 |   |   |